Socomoec Isolator
Characteristics
With new look handles, our Socomec industrial switchgear range is fully rated at AC23 and protected to IP54/ 55. Rotary Isolators are also available in 3 and 4 poles. For any questions or queries, please contact our direct sales line on 0845 226 7125.
| Product Code |
421020 |
421032 |
421063 |
421100 |
421160 |
421200 |
421250 |
421400 |
421630 |
421800 |
| Thermal current lth (40 ˚C) |
20 A |
32 A |
63 A |
100 A |
160 A |
200 A |
250 A |
400 A |
630 A |
800 A |
| Rated insulation voltage Ui (V) |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
1000 |
1000 |
1000 |
| Rated impulse withstand Uimp (kV) |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
12 |
12 |
12 |
Rated operation
currents le(A) |
|
|
|
|
|
|
|
|
|
|
| Rated voltage |
Load duty cat. |
A |
A |
A |
A |
A/B |
A/B |
A/B |
A/B |
A/B |
A/B* |
| 400 VAC |
AC-21 |
20 |
32 |
63 |
100 |
160/160 |
200/200 |
250/250 |
400/400 |
630/630 |
800/800 |
| 400 VAC |
AC-22 |
20 |
32 |
63 |
100 |
160/160 |
200/200 |
250/250 |
400/400 |
630/630 |
800/800 |
| 400 VAC |
AC-23 |
20 |
32 |
63 |
80 |
160/160 |
200/200 |
250/250 |
400/400 |
500/630 |
800/800 |
| 500 VAC |
AC-21 |
20 |
32 |
63 |
100 |
160/160 |
200/200 |
250/250 |
400/400 |
630/630 |
800/800 |
| 500 VAC |
AC-22 |
20 |
32 |
63 |
100 |
160/160 |
200/200 |
250/250 |
400/400 |
500/500 |
800/800 |
| 500 VAC |
AC-23 |
16 |
25 |
50 |
63 |
160/160 |
200/200 |
200/250 |
315/315 |
315/315 |
630/800 |
| 690 VAC |
AC-20 |
- |
- |
- |
- |
160/160 |
200/200 |
250/250 |
400/400 |
630/630 |
800/800 |
| 690 VAC |
AC-21 |
20 |
32 |
63 |
100 |
160/160 |
200/200 |
200/250 |
400/400 |
500/500 |
800/800 |
| 690 VAC |
AC-22 |
20 |
32 |
63 |
100 |
160/160 |
160/160 |
125/160 |
250/315 |
315/315 |
800/800 |
| 690 VAC |
AC-23 |
16 |
20 |
50 |
50 |
63/80 |
63/80 |
100/125 |
160/200 |
160/200 |
200/250 |
| Operational power without pre-break |
| at 400 VAC - AC in AC-3 (kW) |
5.5 |
9 |
18.5 |
30 |
- |
- |
- |
- |
- |
- |
| at 400 VAC - AC in AC-23 A (kW) |
9 |
15 |
30 |
40 |
80/80 |
100/100 |
132/132 |
220/220 |
280/280 |
450/450 |
| at 500 VAC - AC in AC-3 (kW) |
7.5 |
11 |
18.5 |
22 |
- |
- |
- |
- |
- |
- |
| at 500 VAC - AC in AC-23 A (kW) |
9 |
15 |
33 |
40 |
110/110 |
140/140 |
140/160 |
220/220 |
220/220 |
450/560 |
| at 690 VAC - AC in AC-3 (kW) |
9 |
11 |
18.5 |
22 |
- |
- |
- |
- |
- |
- |
| at 690 VAC - AC in AC-23 A (kW) |
11 |
15 |
45 |
45 |
55/75 |
55/75 |
90/110 |
150/185 |
150/185 |
185/220 |
| Fuse protected short-circuit withstand (kA rms prospective) |
| Short circuit current (kA rms) |
50 |
50 |
25 |
25 |
50 |
50 |
50 |
100 |
70 |
50 |
| Associated fuse rating (A) |
20 |
32 |
63 |
100 |
160 |
160 |
250 |
400 |
630 |
800 |
| Short-time withstand 1s l (A rms) |
1260 |
1260 |
1500 |
1500 |
4000 |
4000 |
9000 |
13000 |
13000 |
26000 |
Short-circuit
making capacity (kA peak) |
5.9 |
5.9 |
9.6 |
9.6 |
16 |
16 |
30 |
45 |
45 |
55 |
| Connection & Mechanical Characteristics |
| Minimum Cu cable section (mm2) |
2.5 |
4 |
10 |
25 |
10 |
10 |
95 |
185 |
2 x 150 |
2 x 185 |
| Maximum Cu cable section (mm2) |
16 |
16 |
50 |
50 |
95 |
95 |
150 |
240 |
2 x 300 |
2 x 300 |
| Minimum tightening torque (Nm) |
2 |
2 |
4 |
4 |
9 |
9 |
20 |
20 |
- |
- |
| Endurance (no. operating cycles) |
100000 |
100000 |
30000 |
30000 |
10000 |
10000 |
100000 |
5000 |
5000 |
5000 |
| Stud Size |
- |
- |
- |
- |
M8 |
M8 |
M10 |
M10 |
M12 |
M14 |
| Extension Box |
- |
- |
- |
- |
- |
- |
EX03 |
EX04 |
EX04 |
EX05 |
*A = Frequent Operation B = Infrequent operation
Back to top